Single phase, Single phase zero crossing, Two-wire three-phase zero crossing (SP、SZ、TZ)
Connector pin | Connector No . | Description | Notes |
---|---|---|---|
TB-01 | FS | Detection of the fuse burn down | The connection from power to loading must be connected back to the FS side. |
TB-02 | M | +5VDC | Only for this control board, not for other use positive control signal input. |
TB-03 | + | Positive control signal input | The default setting is 4~20mA when the sticker is not marked. |
TB-04 | - | Standard analog signal voltage | |
TB-05 | E3 | Connected to the VR 3rd pin of the outside potentiometer | Adjustable output 0~100%, Please elimi -nate the shorted copper wire between E3 and E2 when using the outside potentiometer with VR. (2~10KΩ ) |
TB-06 | E2 | Connected to the VR 2nd pin of the outside potentiometer | |
TB-07 | E1 | Connected to the VR 1st pin of the outside potentiometer | |
TB-08 | NC | Alarm connector output (normal close) | 227VAC 2A. Connector capacity 125VAC 2A. 30VAC 2A. |
TB-09 | COM | Alarm connector output (common point) | |
TB-10 | NO | Alarm connector output (normal open) | |
TB-11 | AC1 | Auxiliary power source | Please refer to the stick for the auxiliary power and voltage. |
Three-wire three-phase angle, Three-wire three-phase zero crossing (TP、ZZ)
Connector pin | Connector No . | Description | Notes |
---|---|---|---|
TB-01 | ‧ | Empty pin | Do not connect. |
TB-02 | M | +5VDC | Only for this control board, not for other use positive control signal input. |
TB-03 | + | Positive control signal input | The default setting is 4~20mA when the sticker is not marked. |
TB-04 | - | Standard analog signal voltage | |
TB-05 | E3 | Connected to the VR 3rd pin of the outside potentiometer | Adjustable output 0~100%, Please elimi -nate the shorted copper wire between E3 and E2 when using the outside potentiometer with VR. (2~10KΩ ) |
TB-06 | E2 | Connected to the VR 2nd pin of the outside potentiometer | |
TB-07 | E1 | Connected to the VR 1st pin of the outside potentiometer | |
TB-08 | NC | Alarm connector output (normal close) | 227VAC 2A Connector capacity 125VAC 2A 30VAC 2A |
TB-09 | COM | Alarm connector output (common point) | |
TB-10 | NO | Alarm connector output (normal open) | |
TB-11 | AC1 | Auxiliary power source | Please refer to the stick for the auxiliary power and voltage. |
TB-12 | AC2 |
Rated current | 30A | 45A | 60A | 80A | 100A |
Fuse | 40ET | 63ET | 660GH-80 | 660GH-100ULTC | 660GH-125 |
Brand | Bussmann | Bussmann | Bussmann | Bussmann | HINODE |
Rated current | 125A | 150A | 180A | 230A | 300A |
Fuse | 660GH-80*2 | 660GH-100ULTC*2 | 660GH-125*2 | 250FM | 315FM |
Brand | Bussmann | Bussmann | HINODE | Bussmann | Bussmann |
Rated current | 380A | 450A | 580A | 720A |
Fuse | 660GH-400 | 250FM*2 | 315FM*2 | 660GH-400*2 |
Brand | HINODE | Bussmann | Bussmann | HINODE |